AOIP-monofunction panel meter for electrical measurements (Model:VNE2)

5
632
Vui lòng liên hệ với chúng tôi– chúng tôi sẽ liên hệ lại với khách hàng bằng điện thoại hoặc email.
Lưu ý: Tham khảo ý kiến của nhân viên INO sẽ giúp bạn tiết kiệm được thời gian và chi phí khi cần mua sắm. ​​Với sự tư vấn của chúng tôi, bạn sẽ không gặp khó khăn khi tìm hiểu về đặc tính của sản phẩm cần mua.

VNE2 is a monofunction 2,000 point digital panel meter 72 x 24 mm for electrical measurements in voltage, current and process signals. They are particularly adapted to measurements in industrial areas: robust housing, connection through a removable screwing connector, high immunity to external noises, several types of power supply. AC current measurement can be performed using an external transformer insuring a good insulation to the instrument in regards to line potentials.

  • Panel meter size: 72 mm x 24 mm
  • IP40 protected
  • Measurement and display of:
    • DC and AC voltage up to 650 V
    • DC current up to 1,000 A with an external shunt
    • AC current up to 200 A
    • Process
  • 9 different power supplies available

Electrical measurement indicator

Type Range Resolution Accuracy (1 year)
(23°C ± 1°C)
Input impedance Comment
DC voltage 200 mV
2 V
20 V
200 V
650 V
100 μV
1 mV
10 mV
100 mV
1 V
0.1% + 100 μV
0.1% + 1 mV
0.1% + 10 mV
0.1% + 0.1 V
0.1% + 1 V
> 100 MΩ
1.1 MΩ
1 MΩ
1 MΩ
10 MΩ
Optional decimal point command
DC current On request
2 A
100 mV / 1000 pts
1 mA
0.2% + 1 mA Shunt 100 mV
0.1 Ω
External Shunt 10 – 100 – 1 000 A
or internal 2 – 20 – 200 mA
AC voltage 650 V 1 V 2 V 900 kΩ Band-width
40 Hz to 400 Hz
AC current 2 A
20 A
200 A

On request

1 mA
10 mA
100 mA
100 mV / 1000 pts
1% + 2 mA
1% + 20 mA
1% + 0.2 A
0.3% + 2
900 kΩ Delivered with transformer (2 – 20 ou 200 A) >For secondary of CT 1 or 5A non-included
Process signals with scaling 0 – 5 V
0 – 10 V
4 – 20 mA
0 – 20 mA
Display ± 2000
points
For scale begin and end
0.1 % of
scale end + 1
1 MΩ
1 MΩ
50 Ω
50 Ω
2 models, input and scale defined with order,
can be modified by user (D51 model is set in
factory: 4-20 mA/0-100 %). an analog output is
available as option.

Temperature coefficient: ≤ accuracy/10°C
Common rejection mode: ³ 110 dB at 50 Hz
Serial rejection mode: ³ 60 dB at 50 Hz

Further features

Linear analogue output 1 mV / digit
Acceptable load: ³  2kW 
Non insulated analogue output
External decimal dot commutation Command for V- models
Current transformer Suitable transformer is supplied with I 33, I 34 and I 35 models.
Primary 2 A, 20 A or 200 A.
Secondary 1 A.
200 mV on 0.2 Ω shunt.
Accuracy class 0.5 for 1 VA power
Frequency 50 / 60 Hz.
Primary connection by plugs for 2 A and 20 A ranges and metal
cable gland (∅<12mm) for 200 A range.
Zeroing and polarity Automatic
Sampling rate 2.5 samples / s